UPS scripts
version for ROS 3.x
more details: [1]
<math># UPS-Script powerfail
- (c) steinmann und weidinger OEG
- www.stone-rich.at
- Watches ups status and sends emails on powerfail and battery low.
- This script will FAIL if:
- - Policies write, test, and read are not set
- - The system name contains non-standard characters (space, /, ...)
- - The UPS is not named ups1
- This script was tested on 3.0rc5.
- user-configurable parameters below:
- local mailserver [:resolve mailserver]
- local mailfrom "from@domain.xy"
- local mailto "noc@xyz.xy"
- do NOT make changes below!
- local battalarm 15
- local battok 40
- global flagonbatt
- global flagbattlow
- local curonbatt
- local curcharge
- local sysname [/system identity get name]
- local datetime ([/system clock get date] . " " . [/system clock get time])
- First run? If so, we need to initialize the global flags
- if (("-" . $flagonbatt)="-") do={:set flagonbatt 0}
- if (("-" . $flagbattlow)="-") do={:set flagbattlow 0}
- set curonbatt false
- set curcharge 100
/system ups monitor [/system ups find name="ups1"] once do={:set curonbatt $"on-battery"; :set curcharge $"battery-charge"}
- if (($curonbatt) && ($flagonbatt=0)) do={
:set flagonbatt 1
/tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Power failure!") body=($sysname . " is on battery since " . $datetime)
:log info ("Power-Fail: EMail sent to " . $mailto)
}
- if ((!$curonbatt) && ($flagonbatt=1)) do={
:set flagonbatt 0
/tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Power is back") body=($sysname . " is back on power since " . $datetime)
:log info ("Power-Restore: Email sent to " . $mailto)
}
- if (($curcharge <= $battalarm) && ($flagbattlow=0)) do={
:set flagbattlow 1
/tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Low battery!") body=($sysname . " battery is at " . $curcharge . "%! " . $datetime)
:log info ("Batt-Low: Email sent to " . $mailto)
}
- if (($curcharge >= $battok) && ($flagbattlow=1)) do={
:set flagbattlow 0
/tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Battery recharged") body=($sysname . " Battery recharged to " . $curcharge . "% " . $datetime)
:log info ("Batt-Recharged: Email sent to " . $mailto)
} </math>
version for ROS 2.9x:
# UPS-Script powerfail # (c) steinmann und weidinger OEG # www.stone-rich.at # # Watches ups status and sends emails on powerfail and battery low. # This script will FAIL if: # - Policies write, test, and read are not set # - The system name contains non-standard characters (space, /, ...) # - The UPS is not named ups1 # # This script will not run on 3.x beta!! :set mailserver [:resolve mailserver] :set mailto "to@domain.com" :set mailfrom "from@doamin.xy" :set battalarm 15 :set battok 40 :set sysname [/system identity get name] :set datetime ([/system clock get date] . " " . [/system clock get time]) # First run? If so, we need to initialize the global flags :if (("-" . $flagonbatt)="-") do {:global flagonbatt 0} :if (("-" . $flagbattlow)="-") do {:global flagbattlow 0} :set curonbatt false :set curcharge 100 /system ups monitor [/system ups find name "ups1"] once do {:set curonbatt $on-battery; :set curcharge $battery-charge} :if (($curonbatt) && ($flagonbatt=0)) do { :global flagonbatt 1 /tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Power failure!") body=($sysname . " is on battery since " . $datetime) :log info ("Power-Fail: EMail sent to " . $mailto) } :if ((!$curonbatt) && ($flagonbatt=1)) do { :global flagonbatt 0 /tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Power is back") body=($sysname . " is back on power since " . $datetime) :log info ("Power-Restore: Email sent to " . $mailto) } :if (($curcharge <= $battalarm) && ($flagbattlow=0)) do { :global flagbattlow 1 /tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Low battery!") body=($sysname . " battery is at " . $curcharge . "%! " . $datetime) :log info ("Batt-Low: Email sent to " . $mailto) } :if (($curcharge >= $battok) && ($flagbattlow=1)) do { :global flagbattlow 0 /tool e-mail send from=($mailfrom) to=($mailto) server=($mailserver) subject=($sysname . ": Battery recharged") body=($sysname . " Battery recharged to " . $curcharge . "% " . $datetime) :log info ("Batt-Recharged: Email sent to " . $mailto) }